Brand: R. STAHL AGR. STAHL Series 8146 lighting and heating panels are modular and are therefore available in a large number of standard variants which are available for rapid delivery.
Customer-specific options are also possible.
The circuit breakers are installed beneath a inspection window and can also be actuated from the outside, even under voltage.
The switching position is visible at all times.
Features- Standard versions with short delivery times, customer-specific options possible
- With miniature circuit breaker, tripping characteristic C
- With residual current circuit breaker with overcurrent release, tripping characteristic C
- Rated currents 10, 16, 20, 25 A
1 - 12 of 14 Part Numbers

137111
Standard versions with short delivery times, customer-specific options possible
With miniature circuit breaker, tripping characteristic C
With residual current circuit breaker with overcurrent release, tripping characteristic C
Rated currents 10, 16, 20, 25 A
Ambient Conditions
- Ambient temperature - -20 °C ... +40 °C
- Ambient temperature max. - +40 °C
- Ambient temperature min. - -20 °C
Components
- Built-in unit 2 - 6 x Miniature circuit breaker 1-pole 16A / C / 6 kA
- Entry 1 - 1 x 8161/7-M40-2812
- Entry 2 - 6 x 8161/7-M25-1707
- Entry 3 - 1 x 8161/7-M16-0902
- Locking device present - Yes
Electrical Data
- Frequency range - 50 - 60 Hz
- Layout No. - 01
- Rated operational current - 32.000 A
- Rated operational voltage AC - 230.00 - 400.00 V
Explosion Protection
- Ambient temperature °C - -20 - 40 °C
- Application range (zones) - 1, 2, 21, 22
- ATEX dust certificate - PTB 01 ATEX 1024
- ATEX gas certificate - PTB 01 ATEX 1024
- Certificate EAC - TS RU S-DE.AA71.B.00139
- Certificates - ATEX (PTB), Brazil (ULB), Canada (CSA), Canada (FM), China (NEPSI), EAC (LPE), IECEx (PTB), India (PESO), Korea (KGS), Taiwan (ITRI), USA (FM)
- Dust explosion protection ATEX - II 2 D Ex tb IIIC T80 °C Db
- Dust explosion protection EAC - Ex tb IIIC T80 °C ... T130 °C Db X
- Dust explosion protection IECEx - Ex tb IIIC T80 °C Db
- Gas explosion protection ATEX - II 2 G Ex db eb IIC T6 Gb
- Gas explosion protection EAC - Ex e* IIC...IIA T6 ... T4 Gb X
- Gas explosion protection IECEx - Ex db eb IIC T6 Gb
- IECEX dust certificate - IECEx PTB 06.0090
- IECEX gas certificate - IECEx PTB 06.0090
General
- Functional Description - R. STAHL Series 8146 lighting and heating panels are modular and are therefore available in a large number of standard variants which are available for rapid delivery. Customer-specific options are also possible. The circuit breakers are installed beneath a inspection window and can also be actuated from the outside, even under voltage. The switching position is visible at all times.
- Highlights - Standard versions with short delivery times, customer-specific options possible With miniature circuit breaker, tripping characteristic C With residual current circuit breaker with overcurrent release, tripping characteristic C Rated currents 10, 16, 20, 25 A
- Product Description - Circuit distribution board light With miniature circuit breaker
- Product Type - 8146/5-ExV-01-06L16C1P-T
- Title Product Variant Technical Data - 8146/5-ExV-01-06L16C1P-T stand.licir.dis
- WebCode - 8146D
Mechanical Data
- Connection terminals finely-stranded max. - 35.00 mm²
- Degree of protection (IP) - IP66
- Degree of protection IP (IEC 60529) - IP66
- Depth - 190.000 mm
- Enclosure colour - grey
- Enclosure material - Polyester resin, Glass fibre reinforced
- Flame retardant acc. - IEC/EN 60695, UL 94, ASTM D635
- Height - 681.500 mm
- Impact strength - 7.00 J
- Weight - 25.000 kg
- Width - 340.500 mm

137118
Standard versions with short delivery times, customer-specific options possible
With miniature circuit breaker, tripping characteristic C
With residual current circuit breaker with overcurrent release, tripping characteristic C
Rated currents 10, 16, 20, 25 A

137124
Standard versions with short delivery times, customer-specific options possible
With miniature circuit breaker, tripping characteristic C
With residual current circuit breaker with overcurrent release, tripping characteristic C
Rated currents 10, 16, 20, 25 A
Ambient Conditions
- Ambient temperature - -20 °C ... +40 °C
- Ambient temperature max. - +40 °C
- Ambient temperature min. - -20 °C
Components
- Built-in unit 2 - 18 x Miniature circuit breaker 1-pole 16A / C / 6 kA
- Entry 1 - 1 x 8161/7-M50-3516
- Entry 2 - 18 x 8161/7-M25-1707
- Entry 3 - 1 x 8161/7-M16-0902
- Locking device present - Yes
Electrical Data
- Frequency range - 50 - 60 Hz
- Layout No. - 03
- Rated operational current - 80.000 A
- Rated operational voltage AC - 230.00 - 400.00 V
Explosion Protection
- Ambient temperature °C - -20 - 40 °C
- Application range (zones) - 1, 2, 21, 22
- ATEX dust certificate - PTB 01 ATEX 1024
- ATEX gas certificate - PTB 01 ATEX 1024
- Certificate EAC - TS RU S-DE.AA71.B.00139
- Certificates - ATEX (PTB), Brazil (ULB), Canada (CSA), Canada (FM), China (NEPSI), EAC (LPE), IECEx (PTB), India (PESO), Korea (KGS), Taiwan (ITRI), USA (FM)
- Dust explosion protection ATEX - II 2 D Ex tb IIIC T80 °C Db
- Dust explosion protection EAC - Ex tb IIIC T80 °C ... T130 °C Db X
- Dust explosion protection IECEx - Ex tb IIIC T80 °C Db
- Gas explosion protection ATEX - II 2 G Ex db eb IIC T6 Gb
- Gas explosion protection EAC - Ex e* IIC...IIA T6 ... T4 Gb X
- Gas explosion protection IECEx - Ex db eb IIC T6 Gb
- IECEX dust certificate - IECEx PTB 06.0090
- IECEX gas certificate - IECEx PTB 06.0090
General
- Functional Description - R. STAHL Series 8146 lighting and heating panels are modular and are therefore available in a large number of standard variants which are available for rapid delivery. Customer-specific options are also possible. The circuit breakers are installed beneath a inspection window and can also be actuated from the outside, even under voltage. The switching position is visible at all times.
- Highlights - Standard versions with short delivery times, customer-specific options possible With miniature circuit breaker, tripping characteristic C With residual current circuit breaker with overcurrent release, tripping characteristic C Rated currents 10, 16, 20, 25 A
- Product Description - Circuit distribution board light With miniature circuit breaker
- Product Type - 8146/5-ExV-03-18L16C1P-T
- Title Product Variant Technical Data - 8146/5-ExV-03-18L16C1P-T stand.licir.dis
- WebCode - 8146D
Mechanical Data
- Connection terminals finely-stranded max. - 35.00 mm²
- Degree of protection (IP) - IP66
- Degree of protection IP (IEC 60529) - IP66
- Depth - 190.000 mm
- Enclosure colour - grey
- Enclosure material - Polyester resin, Glass fibre reinforced
- Flame retardant acc. - IEC/EN 60695, UL 94, ASTM D635
- Height - 681.500 mm
- Impact strength - 7.00 J
- Weight - 50.000 kg
- Width - 681.500 mm

137130
Standard versions with short delivery times, customer-specific options possible
With miniature circuit breaker, tripping characteristic C
With residual current circuit breaker with overcurrent release, tripping characteristic C
Rated currents 10, 16, 20, 25 A
Ambient Conditions
- Ambient temperature - -20 °C ... +40 °C
- Ambient temperature max. - +40 °C
- Ambient temperature min. - -20 °C
Components
- Built-in unit 2 - 24 x Miniature circuit breaker 1-pole 16A / C / 6 kA
- Entry 1 - 1 x 8161/7-M50-3516
- Entry 2 - 24 x 8161/7-M25-1707
- Entry 3 - 1 x 8161/7-M16-0902
- Locking device present - Yes
Electrical Data
- Frequency range - 50 - 60 Hz
- Layout No. - 04
- Rated operational current - 80.000 A
- Rated operational voltage AC - 230.00 - 400.00 V
Explosion Protection
- Ambient temperature °C - -20 - 40 °C
- Application range (zones) - 1, 2, 21, 22
- ATEX dust certificate - PTB 01 ATEX 1024
- ATEX gas certificate - PTB 01 ATEX 1024
- Certificate EAC - TS RU S-DE.AA71.B.00139
- Certificates - ATEX (PTB), Brazil (ULB), Canada (CSA), Canada (FM), China (NEPSI), EAC (LPE), IECEx (PTB), India (PESO), Korea (KGS), Taiwan (ITRI), USA (FM)
- Dust explosion protection ATEX - II 2 D Ex tb IIIC T80 °C Db
- Dust explosion protection EAC - Ex tb IIIC T80 °C ... T130 °C Db X
- Dust explosion protection IECEx - Ex tb IIIC T80 °C Db
- Gas explosion protection ATEX - II 2 G Ex db eb IIC T6 Gb
- Gas explosion protection EAC - Ex e* IIC...IIA T6 ... T4 Gb X
- Gas explosion protection IECEx - Ex db eb IIC T6 Gb
- IECEX dust certificate - IECEx PTB 06.0090
- IECEX gas certificate - IECEx PTB 06.0090
General
- Functional Description - R. STAHL Series 8146 lighting and heating panels are modular and are therefore available in a large number of standard variants which are available for rapid delivery. Customer-specific options are also possible. The circuit breakers are installed beneath a inspection window and can also be actuated from the outside, even under voltage. The switching position is visible at all times.
- Highlights - Standard versions with short delivery times, customer-specific options possible With miniature circuit breaker, tripping characteristic C With residual current circuit breaker with overcurrent release, tripping characteristic C Rated currents 10, 16, 20, 25 A
- Product Description - Circuit distribution board light With miniature circuit breaker
- Product Type - 8146/5-ExV-04-24L16C1P-T
- Title Product Variant Technical Data - 8146/5-ExV-04-24L16C1P-T stand.licir.dis
- WebCode - 8146D
Mechanical Data
- Connection terminals finely-stranded max. - 35.00 mm²
- Degree of protection (IP) - IP66
- Degree of protection IP (IEC 60529) - IP66
- Depth - 240.000 mm
- Enclosure colour - grey
- Enclosure material - Polyester resin, Glass fibre reinforced
- Flame retardant acc. - IEC/EN 60695, UL 94, ASTM D635
- Height - 684.000 mm
- Impact strength - 7.00 J
- Weight - 70.000 kg
- Width - 1236.000 mm

137135
Standard versions with short delivery times, customer-specific options possible
With miniature circuit breaker, tripping characteristic C
With residual current circuit breaker with overcurrent release, tripping characteristic C
Rated currents 10, 16, 20, 25 A
Ambient Conditions
- Ambient temperature - -20 °C ... +40 °C
- Ambient temperature max. - +40 °C
- Ambient temperature min. - -20 °C
Components
- Built-in unit 2 - 6 x Miniature circuit breaker 1-pole 16A / C / 6 kA
- Entry 1 - 1 x 8161/7-M40-2812
- Entry 2 - 6 x 8161/7-M25-1707
- Entry 3 - 1 x 8161/7-M16-0902
- Locking device present - Yes
Electrical Data
- Frequency range - 50 - 60 Hz
- Layout No. - 06
- Rated operational current - 32.000 A
- Rated operational voltage AC - 230.00 - 400.00 V
Explosion Protection
- Ambient temperature °C - -20 - 40 °C
- Application range (zones) - 1, 2, 21, 22
- ATEX dust certificate - PTB 01 ATEX 1024
- ATEX gas certificate - PTB 01 ATEX 1024
- Certificate EAC - TS RU S-DE.AA71.B.00139
- Certificates - ATEX (PTB), Brazil (ULB), Canada (CSA), Canada (FM), China (NEPSI), EAC (LPE), IECEx (PTB), India (PESO), Korea (KGS), Taiwan (ITRI), USA (FM)
- Dust explosion protection ATEX - II 2 D Ex tb IIIC T80 °C Db
- Dust explosion protection EAC - Ex tb IIIC T80 °C ... T130 °C Db X
- Dust explosion protection IECEx - Ex tb IIIC T80 °C Db
- Gas explosion protection ATEX - II 2 G Ex db eb IIC T6 Gb
- Gas explosion protection EAC - Ex e* IIC...IIA T6 ... T4 Gb X
- Gas explosion protection IECEx - Ex db eb IIC T6 Gb
- IECEX dust certificate - IECEx PTB 06.0090
- IECEX gas certificate - IECEx PTB 06.0090
General
- Functional Description - R. STAHL Series 8146 lighting and heating panels are modular and are therefore available in a large number of standard variants which are available for rapid delivery. Customer-specific options are also possible. The circuit breakers are installed beneath a inspection window and can also be actuated from the outside, even under voltage. The switching position is visible at all times.
- Highlights - Standard versions with short delivery times, customer-specific options possible With miniature circuit breaker, tripping characteristic C With residual current circuit breaker with overcurrent release, tripping characteristic C Rated currents 10, 16, 20, 25 A
- Product Description - Circuit distribution board light With miniature circuit breaker
- Product Type - 8146/5-ExV-06-06L16C1P-D
- Title Product Variant Technical Data - 8146/5-ExV-06-06L16C1P-D stand.licir.dis
- WebCode - 8146D
Mechanical Data
- Connection terminals finely-stranded max. - 35.00 mm²
- Degree of protection (IP) - IP66
- Degree of protection IP (IEC 60529) - IP66
- Depth - 190.000 mm
- Enclosure colour - grey
- Enclosure material - Polyester resin, Glass fibre reinforced
- Flame retardant acc. - IEC/EN 60695, UL 94, ASTM D635
- Height - 340.500 mm
- Impact strength - 7.00 J
- Weight - 25.000 kg
- Width - 681.500 mm

137140
Standard versions with short delivery times, customer-specific options possible
With miniature circuit breaker, tripping characteristic C
With residual current circuit breaker with overcurrent release, tripping characteristic C
Rated currents 10, 16, 20, 25 A
Ambient Conditions
- Ambient temperature - -20 °C ... +40 °C
- Ambient temperature max. - +40 °C
- Ambient temperature min. - -20 °C
Components
- Built-in unit 2 - 12 x Miniature circuit breaker 1-pole 16A / C / 6 kA
- Entry 1 - 1 x 8161/7-M50-3516
- Entry 2 - 12 x 8161/7-M25-1707
- Entry 3 - 1 x 8161/7-M16-0902
- Locking device present - Yes
Electrical Data
- Frequency range - 50 - 60 Hz
- Layout No. - 07
- Rated operational current - 64.000 A
- Rated operational voltage AC - 230.00 - 400.00 V
Explosion Protection
- Ambient temperature °C - -20 - 40 °C
- Application range (zones) - 1, 2, 21, 22
- ATEX dust certificate - PTB 01 ATEX 1024
- ATEX gas certificate - PTB 01 ATEX 1024
- Certificate EAC - TS RU S-DE.AA71.B.00139
- Certificates - ATEX (PTB), Brazil (ULB), Canada (CSA), Canada (FM), China (NEPSI), EAC (LPE), IECEx (PTB), India (PESO), Korea (KGS), Taiwan (ITRI), USA (FM)
- Dust explosion protection ATEX - II 2 D Ex tb IIIC T80 °C Db
- Dust explosion protection EAC - Ex tb IIIC T80 °C ... T130 °C Db X
- Dust explosion protection IECEx - Ex tb IIIC T80 °C Db
- Gas explosion protection ATEX - II 2 G Ex db eb IIC T6 Gb
- Gas explosion protection EAC - Ex e* IIC...IIA T6 ... T4 Gb X
- Gas explosion protection IECEx - Ex db eb IIC T6 Gb
- IECEX dust certificate - IECEx PTB 06.0090
- IECEX gas certificate - IECEx PTB 06.0090
General
- Functional Description - R. STAHL Series 8146 lighting and heating panels are modular and are therefore available in a large number of standard variants which are available for rapid delivery. Customer-specific options are also possible. The circuit breakers are installed beneath a inspection window and can also be actuated from the outside, even under voltage. The switching position is visible at all times.
- Highlights - Standard versions with short delivery times, customer-specific options possible With miniature circuit breaker, tripping characteristic C With residual current circuit breaker with overcurrent release, tripping characteristic C Rated currents 10, 16, 20, 25 A
- Product Description - Circuit distribution board light With miniature circuit breaker
- Product Type - 8146/5-ExV-07-12L16C1P-D
- Title Product Variant Technical Data - 8146/5-ExV-07-12L16C1P-D stand.licir.dis
- WebCode - 8146D
Mechanical Data
- Connection terminals finely-stranded max. - 35.00 mm²
- Degree of protection (IP) - IP66
- Degree of protection IP (IEC 60529) - IP66
- Depth - 190.000 mm
- Enclosure colour - grey
- Enclosure material - Polyester resin, Glass fibre reinforced
- Flame retardant acc. - IEC/EN 60695, UL 94, ASTM D635
- Height - 340.500 mm
- Impact strength - 7.00 J
- Weight - 37.000 kg
- Width - 1023.000 mm

137146
Standard versions with short delivery times, customer-specific options possible
With miniature circuit breaker, tripping characteristic C
With residual current circuit breaker with overcurrent release, tripping characteristic C
Rated currents 10, 16, 20, 25 A
Ambient Conditions
- Ambient temperature - -20 °C ... +40 °C
- Ambient temperature max. - +40 °C
- Ambient temperature min. - -20 °C
Components
- Built-in unit 2 - 8 x With residual current circuit breaker 1-pole 16 A+N/30 mA/B/6 kA
- Entry 1 - 1 x 8161/7-M40-2812
- Entry 2 - 8 x 8161/7-M25-1707
- Entry 3 - 1 x 8161/7-M16-0902
- Locking device present - Yes
Electrical Data
- Frequency range - 50 - 60 Hz
- Layout No. - 02
- Rated operational current - 48.000 A
- Rated operational voltage AC - 230.00 - 400.00 V
Explosion Protection
- Ambient temperature °C - -20 - 40 °C
- Application range (zones) - 1, 2, 21, 22
- ATEX dust certificate - PTB 01 ATEX 1024
- ATEX gas certificate - PTB 01 ATEX 1024
- Certificate EAC - TS RU S-DE.AA71.B.00139
- Certificates - ATEX (PTB), Brazil (ULB), Canada (CSA), Canada (FM), China (NEPSI), EAC (LPE), IECEx (PTB), India (PESO), Korea (KGS), Taiwan (ITRI), USA (FM)
- Dust explosion protection ATEX - II 2 D Ex tb IIIC T130 °C Db
- Dust explosion protection EAC - Ex tb IIIC T80 °C ... T130 °C Db X
- Dust explosion protection IECEx - Ex tb IIIC T130 °C Db
- Gas explosion protection ATEX - II 2 G Ex db eb IIC T4 Gb
- Gas explosion protection EAC - Ex e* IIC...IIA T6 ... T4 Gb X
- Gas explosion protection IECEx - Ex db eb IIC T4 Gb
- IECEX dust certificate - IECEx PTB 06.0090
- IECEX gas certificate - IECEx PTB 06.0090
General
- Functional Description - R. STAHL Series 8146 lighting and heating panels are modular and are therefore available in a large number of standard variants which are available for rapid delivery. Customer-specific options are also possible. The circuit breakers are installed beneath a inspection window and can also be actuated from the outside, even under voltage. The switching position is visible at all times.
- Highlights - Standard versions with short delivery times, customer-specific options possible With miniature circuit breaker, tripping characteristic C With residual current circuit breaker with overcurrent release, tripping characteristic C Rated currents 10, 16, 20, 25 A
- Product Description - Heating circuit distribution boards With residual current circuit breaker With overcurrent release
- Product Type - 8146/5-ExV-02-08H16B1N-T
- Title Product Variant Technical Data - 8146/5-ExV-02-08H16B1N-T stand.licir.dis
- WebCode - 8146D
Mechanical Data
- Connection terminals finely-stranded max. - 35.00 mm²
- Degree of protection (IP) - IP66
- Degree of protection IP (IEC 60529) - IP66
- Depth - 190.000 mm
- Enclosure colour - grey
- Enclosure material - Polyester resin, Glass fibre reinforced
- Flame retardant acc. - IEC/EN 60695, UL 94, ASTM D635
- Height - 681.500 mm
- Impact strength - 7.00 J
- Weight - 37.000 kg
- Width - 681.500 mm

137152
Standard versions with short delivery times, customer-specific options possible
With miniature circuit breaker, tripping characteristic C
With residual current circuit breaker with overcurrent release, tripping characteristic C
Rated currents 10, 16, 20, 25 A
Ambient Conditions
- Ambient temperature - -20 °C ... +40 °C
- Ambient temperature max. - +40 °C
- Ambient temperature min. - -20 °C
Components
- Built-in unit 2 - 12 x With residual current circuit breaker 1-pole 16 A+N/30 mA/B/6 kA
- Entry 1 - 1 x 8161/7-M50-3516
- Entry 2 - 12 x 8161/7-M25-1707
- Entry 3 - 1 x 8161/7-M16-0902
- Locking device present - Yes
Electrical Data
- Frequency range - 50 - 60 Hz
- Layout No. - 03
- Rated operational current - 64.000 A
- Rated operational voltage AC - 230.00 - 400.00 V
Explosion Protection
- Ambient temperature °C - -20 - 40 °C
- Application range (zones) - 1, 2, 21, 22
- ATEX dust certificate - PTB 01 ATEX 1024
- ATEX gas certificate - PTB 01 ATEX 1024
- Certificate EAC - TS RU S-DE.AA71.B.00139
- Certificates - ATEX (PTB), Brazil (ULB), Canada (CSA), Canada (FM), China (NEPSI), EAC (LPE), IECEx (PTB), India (PESO), Korea (KGS), Taiwan (ITRI), USA (FM)
- Dust explosion protection ATEX - II 2 D Ex tb IIIC T130 °C Db
- Dust explosion protection EAC - Ex tb IIIC T80 °C ... T130 °C Db X
- Dust explosion protection IECEx - Ex tb IIIC T130 °C Db
- Gas explosion protection ATEX - II 2 G Ex db eb IIC T4 Gb
- Gas explosion protection EAC - Ex e* IIC...IIA T6 ... T4 Gb X
- Gas explosion protection IECEx - Ex db eb IIC T4 Gb
- IECEX dust certificate - IECEx PTB 06.0090
- IECEX gas certificate - IECEx PTB 06.0090
General
- Functional Description - R. STAHL Series 8146 lighting and heating panels are modular and are therefore available in a large number of standard variants which are available for rapid delivery. Customer-specific options are also possible. The circuit breakers are installed beneath a inspection window and can also be actuated from the outside, even under voltage. The switching position is visible at all times.
- Highlights - Standard versions with short delivery times, customer-specific options possible With miniature circuit breaker, tripping characteristic C With residual current circuit breaker with overcurrent release, tripping characteristic C Rated currents 10, 16, 20, 25 A
- Product Description - Heating circuit distribution boards With residual current circuit breaker With overcurrent release
- Product Type - 8146/5-ExV-03-12H16B1N-T
- Title Product Variant Technical Data - 8146/5-ExV-03-12H16B1N-T stand.licir.dis
- WebCode - 8146D
Mechanical Data
- Connection terminals finely-stranded max. - 35.00 mm²
- Degree of protection (IP) - IP66
- Degree of protection IP (IEC 60529) - IP66
- Depth - 240.000 mm
- Enclosure colour - grey
- Enclosure material - Polyester resin, Glass fibre reinforced
- Flame retardant acc. - IEC/EN 60695, UL 94, ASTM D635
- Height - 684.000 mm
- Impact strength - 7.00 J
- Weight - 50.000 kg
- Width - 1236.000 mm

137157
Standard versions with short delivery times, customer-specific options possible
With miniature circuit breaker, tripping characteristic C
With residual current circuit breaker with overcurrent release, tripping characteristic C
Rated currents 10, 16, 20, 25 A
Ambient Conditions
- Ambient temperature - -20 °C ... +40 °C
- Ambient temperature max. - +40 °C
- Ambient temperature min. - -20 °C
Components
- Built-in unit 2 - 24 x With residual current circuit breaker 1-pole 16 A+N/30 mA/B/6 kA
- Entry 1 - 1 x 8161/7-M50-3516
- Entry 2 - 24 x 8161/7-M25-1707
- Entry 3 - 1 x 8161/7-M16-0902
- Locking device present - Yes
Electrical Data
- Frequency range - 50 - 60 Hz
- Layout No. - 05
- Rated operational current - 80.000 A
- Rated operational voltage AC - 230.00 - 400.00 V
Explosion Protection
- Ambient temperature °C - -20 - 40 °C
- Application range (zones) - 1, 2, 21, 22
- ATEX dust certificate - PTB 01 ATEX 1024
- ATEX gas certificate - PTB 01 ATEX 1024
- Certificate EAC - TS RU S-DE.AA71.B.00139
- Certificates - ATEX (PTB), Brazil (ULB), Canada (CSA), Canada (FM), China (NEPSI), EAC (LPE), IECEx (PTB), India (PESO), Korea (KGS), Taiwan (ITRI), USA (FM)
- Dust explosion protection ATEX - II 2 D Ex tb IIIC T130 °C Db
- Dust explosion protection EAC - Ex tb IIIC T80 °C ... T130 °C Db X
- Dust explosion protection IECEx - Ex tb IIIC T130 °C Db
- Gas explosion protection ATEX - II 2 G Ex db eb IIC T4 Gb
- Gas explosion protection EAC - Ex e* IIC...IIA T6 ... T4 Gb X
- Gas explosion protection IECEx - Ex db eb IIC T4 Gb
- IECEX dust certificate - IECEx PTB 06.0090
- IECEX gas certificate - IECEx PTB 06.0090
General
- Functional Description - R. STAHL Series 8146 lighting and heating panels are modular and are therefore available in a large number of standard variants which are available for rapid delivery. Customer-specific options are also possible. The circuit breakers are installed beneath a inspection window and can also be actuated from the outside, even under voltage. The switching position is visible at all times.
- Highlights - Standard versions with short delivery times, customer-specific options possible With miniature circuit breaker, tripping characteristic C With residual current circuit breaker with overcurrent release, tripping characteristic C Rated currents 10, 16, 20, 25 A
- Product Description - Heating circuit distribution boards With residual current circuit breaker With overcurrent release
- Product Type - 8146/5-ExV-05-24H16B1N-T
- Title Product Variant Technical Data - 8146/5-ExV-05-24H16B1N-T stan.ht.cir.dis
- WebCode - 8146D
Mechanical Data
- Connection terminals finely-stranded max. - 35.00 mm²
- Degree of protection (IP) - IP66
- Degree of protection IP (IEC 60529) - IP66
- Depth - 240.000 mm
- Enclosure colour - grey
- Enclosure material - Polyester resin, Glass fibre reinforced
- Flame retardant acc. - IEC/EN 60695, UL 94, ASTM D635
- Height - 684.000 mm
- Impact strength - 7.00 J
- Weight - 95.000 kg
- Width - 1578.000 mm

137161
Standard versions with short delivery times, customer-specific options possible
With miniature circuit breaker, tripping characteristic C
With residual current circuit breaker with overcurrent release, tripping characteristic C
Rated currents 10, 16, 20, 25 A
Ambient Conditions
- Ambient temperature - -20 °C ... +40 °C
- Ambient temperature max. - +40 °C
- Ambient temperature min. - -20 °C
Components
- Built-in unit 2 - 8 x With residual current circuit breaker 1-pole 16 A+N/30 mA/C/6 kA
- Entry 1 - 1 x 8161/7-M40-2812
- Entry 2 - 8 x 8161/7-M25-1707
- Entry 3 - 1 x 8161/7-M16-0902
- Locking device present - Yes
Electrical Data
- Frequency range - 50 - 60 Hz
- Layout No. - 02
- Rated operational current - 48.000 A
- Rated operational voltage AC - 230.00 - 400.00 V
Explosion Protection
- Ambient temperature °C - -20 - 40 °C
- Application range (zones) - 1, 2, 21, 22
- ATEX dust certificate - PTB 01 ATEX 1024
- ATEX gas certificate - PTB 01 ATEX 1024
- Certificate EAC - TS RU S-DE.AA71.B.00139
- Certificates - ATEX (PTB), Brazil (ULB), Canada (CSA), Canada (FM), China (NEPSI), EAC (LPE), IECEx (PTB), India (PESO), Korea (KGS), Taiwan (ITRI), USA (FM)
- Dust explosion protection ATEX - II 2 D Ex tb IIIC T130 °C Db
- Dust explosion protection EAC - Ex tb IIIC T80 °C ... T130 °C Db X
- Dust explosion protection IECEx - Ex tb IIIC T130 °C Db
- Gas explosion protection ATEX - II 2 G Ex db eb IIC T4 Gb
- Gas explosion protection EAC - Ex e* IIC...IIA T6 ... T4 Gb X
- Gas explosion protection IECEx - Ex db eb IIC T4 Gb
- IECEX dust certificate - IECEx PTB 06.0090
- IECEX gas certificate - IECEx PTB 06.0090
General
- Functional Description - R. STAHL Series 8146 lighting and heating panels are modular and are therefore available in a large number of standard variants which are available for rapid delivery. Customer-specific options are also possible. The circuit breakers are installed beneath a inspection window and can also be actuated from the outside, even under voltage. The switching position is visible at all times.
- Highlights - Standard versions with short delivery times, customer-specific options possible With miniature circuit breaker, tripping characteristic C With residual current circuit breaker with overcurrent release, tripping characteristic C Rated currents 10, 16, 20, 25 A
- Product Description - Heating circuit distribution boards With residual current circuit breaker With overcurrent release
- Product Type - 8146/5-ExV-02-08H16C1N-T
- Title Product Variant Technical Data - 8146/5-ExV-02-08H16C1N-T stan.ht.cir.dis
- WebCode - 8146D
Mechanical Data
- Connection terminals finely-stranded max. - 35.00 mm²
- Degree of protection (IP) - IP66
- Degree of protection IP (IEC 60529) - IP66
- Depth - 190.000 mm
- Enclosure colour - grey
- Enclosure material - Polyester resin, Glass fibre reinforced
- Flame retardant acc. - IEC/EN 60695, UL 94, ASTM D635
- Height - 681.500 mm
- Impact strength - 7.00 J
- Weight - 37.000 kg
- Width - 681.500 mm

137164
Standard versions with short delivery times, customer-specific options possible
With miniature circuit breaker, tripping characteristic C
With residual current circuit breaker with overcurrent release, tripping characteristic C
Rated currents 10, 16, 20, 25 A
Ambient Conditions
- Ambient temperature - -20 °C ... +40 °C
- Ambient temperature max. - +40 °C
- Ambient temperature min. - -20 °C
Components
- Built-in unit 2 - 12 x With residual current circuit breaker 1-pole 16 A+N/30 mA/C/6 kA
- Entry 1 - 1 x 8161/7-M50-3516
- Entry 2 - 12 x 8161/7-M25-1707
- Entry 3 - 1 x 8161/7-M16-0902
- Locking device present - Yes
Electrical Data
- Frequency range - 50 - 60 Hz
- Layout No. - 03
- Rated operational current - 64.000 A
- Rated operational voltage AC - 230.00 - 400.00 V
Explosion Protection
- Ambient temperature °C - -20 - 40 °C
- Application range (zones) - 1, 2, 21, 22
- ATEX dust certificate - PTB 01 ATEX 1024
- ATEX gas certificate - PTB 01 ATEX 1024
- Certificate EAC - TS RU S-DE.AA71.B.00139
- Certificates - ATEX (PTB), Brazil (ULB), Canada (CSA), Canada (FM), China (NEPSI), EAC (LPE), IECEx (PTB), India (PESO), Korea (KGS), Taiwan (ITRI), USA (FM)
- Dust explosion protection ATEX - II 2 D Ex tb IIIC T130 °C Db
- Dust explosion protection EAC - Ex tb IIIC T80 °C ... T130 °C Db X
- Dust explosion protection IECEx - Ex tb IIIC T130 °C Db
- Gas explosion protection ATEX - II 2 G Ex db eb IIC T4 Gb
- Gas explosion protection EAC - Ex e* IIC...IIA T6 ... T4 Gb X
- Gas explosion protection IECEx - Ex db eb IIC T4 Gb
- IECEX dust certificate - IECEx PTB 06.0090
- IECEX gas certificate - IECEx PTB 06.0090
General
- Functional Description - R. STAHL Series 8146 lighting and heating panels are modular and are therefore available in a large number of standard variants which are available for rapid delivery. Customer-specific options are also possible. The circuit breakers are installed beneath a inspection window and can also be actuated from the outside, even under voltage. The switching position is visible at all times.
- Highlights - Standard versions with short delivery times, customer-specific options possible With miniature circuit breaker, tripping characteristic C With residual current circuit breaker with overcurrent release, tripping characteristic C Rated currents 10, 16, 20, 25 A
- Product Description - Heating circuit distribution boards With residual current circuit breaker With overcurrent release
- Product Type - 8146/5-ExV-03-12H16C1N-T
- Title Product Variant Technical Data - 8146/5-ExV-03-12H16C1N-T stan.ht.cir.dis
- WebCode - 8146D
Mechanical Data
- Connection terminals finely-stranded max. - 35.00 mm²
- Degree of protection (IP) - IP66
- Degree of protection IP (IEC 60529) - IP66
- Depth - 240.000 mm
- Enclosure colour - grey
- Enclosure material - Polyester resin, Glass fibre reinforced
- Flame retardant acc. - IEC/EN 60695, UL 94, ASTM D635
- Height - 684.000 mm
- Impact strength - 7.00 J
- Weight - 50.000 kg
- Width - 1236.000 mm

137167
Standard versions with short delivery times, customer-specific options possible
With miniature circuit breaker, tripping characteristic C
With residual current circuit breaker with overcurrent release, tripping characteristic C
Rated currents 10, 16, 20, 25 A
Ambient Conditions
- Ambient temperature - -20 °C ... +40 °C
- Ambient temperature max. - +40 °C
- Ambient temperature min. - -20 °C
Components
- Built-in unit 2 - 24 x With residual current circuit breaker 1-pole 16 A+N/30 mA/C/6 kA
- Entry 1 - 1 x 8161/7-M50-3516
- Entry 2 - 24 x 8161/7-M25-1707
- Entry 3 - 1 x 8161/7-M16-0902
- Locking device present - Yes
Electrical Data
- Frequency range - 50 - 60 Hz
- Layout No. - 05
- Rated operational current - 80.000 A
- Rated operational voltage AC - 230.00 - 400.00 V
Explosion Protection
- Ambient temperature °C - -20 - 40 °C
- Application range (zones) - 1, 2, 21, 22
- ATEX dust certificate - PTB 01 ATEX 1024
- ATEX gas certificate - PTB 01 ATEX 1024
- Certificate EAC - TS RU S-DE.AA71.B.00139
- Certificates - ATEX (PTB), Brazil (ULB), Canada (CSA), Canada (FM), China (NEPSI), EAC (LPE), IECEx (PTB), India (PESO), Korea (KGS), Taiwan (ITRI), USA (FM)
- Dust explosion protection ATEX - II 2 D Ex tb IIIC T130 °C Db
- Dust explosion protection EAC - Ex tb IIIC T80 °C ... T130 °C Db X
- Dust explosion protection IECEx - Ex tb IIIC T130 °C Db
- Gas explosion protection ATEX - II 2 G Ex db eb IIC T4 Gb
- Gas explosion protection EAC - Ex e* IIC...IIA T6 ... T4 Gb X
- Gas explosion protection IECEx - Ex db eb IIC T4 Gb
- IECEX dust certificate - IECEx PTB 06.0090
- IECEX gas certificate - IECEx PTB 06.0090
General
- Functional Description - R. STAHL Series 8146 lighting and heating panels are modular and are therefore available in a large number of standard variants which are available for rapid delivery. Customer-specific options are also possible. The circuit breakers are installed beneath a inspection window and can also be actuated from the outside, even under voltage. The switching position is visible at all times.
- Highlights - Standard versions with short delivery times, customer-specific options possible With miniature circuit breaker, tripping characteristic C With residual current circuit breaker with overcurrent release, tripping characteristic C Rated currents 10, 16, 20, 25 A
- Product Description - Heating circuit distribution boards With residual current circuit breaker With overcurrent release
- Product Type - 8146/5-ExV-05-24H16C1N-T
- Title Product Variant Technical Data - 8146/5-ExV-05-24H16C1N-T stan.ht.cir.dis
- WebCode - 8146D
Mechanical Data
- Connection terminals finely-stranded max. - 35.00 mm²
- Degree of protection (IP) - IP66
- Degree of protection IP (IEC 60529) - IP66
- Depth - 240.000 mm
- Enclosure colour - grey
- Enclosure material - Polyester resin, Glass fibre reinforced
- Flame retardant acc. - IEC/EN 60695, UL 94, ASTM D635
- Height - 684.000 mm
- Impact strength - 7.00 J
- Weight - 95.000 kg
- Width - 1578.000 mm