Yodify Product Library
Add the Digital Input Output Module Series 9470/32 to your store or catalog
Book Your Demo and See How
or create your store
Digital Input Output Module Series 9470/32
Brand: R. STAHL AGThe 9470/32 series digital input/output module for Zone 1 has 16 channels, which can be used in pairs for Exi operation as inputs for contacts and NAMUR proximity sensors (EN 60947-5-6) or as outputs for indicator lamps and low-power solenoid valves.
Eight inputs can be used for frequencies of up to 20 kHz, and four can be used for detecting the direction of rotation. All inputs/outputs are short-circuit proof and galvanically separated from the system.
Features- Sixteen channels can be used in pairs as inputs or outputs
- Intrinsically safe Ex ia IIC inputs/outputs with line fault monitoring and LED error and status indication for each channel
- Module in Zone 1 can be hot swapped
1 - 1 of 1 Part Numbers

210447
Sixteen channels can be used in pairs as inputs or outputs
intrinsically safe Ex ia IIC inputs/outputs with line fault monitoring and LED error and status indication for each channel
module in Zone 1 can be hot swapped
Ambient Conditions
- Ambient temperature - -40°C ... +75°C
- Ambient temperature max. - +75°C
- Ambient temperature min. - -40°C
- Max. operating height - < 2000 m
- Max. relative humidity - 95% (without condensation)
- Note - (observe operating instructions)
- Storage temperature - -40°C ... +80°C
- storage temperature °C - -40 - 80 °C
- Storage temperature max. - +80°C
- Storage temperature min. - -40°C
Auxiliary power
- Auxiliary power Version - Intrin. safe Ex ia via BusRail
- Current consumption - 120 mA
- Max. power consumption - 2.50 W
- Max. power dissipation of outputs - 2.5 W
- Max. power dissipation outputs - 2.5 W
- Power consumption max. - 2.50 W
- Power supply connection - BusRail types 9494
Device Specific Data
- Counter control - Stop Run Reset
- Counting event - negative slope positive slope
- In. behaviour in case of error - Replacement value "0" replacement value "1" hold (initial value 0) hold (initial value 1)
- Inverting input/output - normal inverted
- LED channel error - LED for each channel, red
- LED channel status - LED for each channel, yellow
- LED group error - "ERR" LED, red
- LED operating state - "RUN" LED, green
- LEDmodule requires maintenance - "M/S" LED, blue
- Line fault monitoring - OFF ON
- Module diagnostics message - ON OFF
- Operat.mode counter/frequency - 0.1 ... 600 Hz 1 Hz ... 20 kHz 1 Hz ... 20 kHz with direction 1 Hz ... 3 kHz Counter 16 bit up/down counter 16 bit up/down counter 32 bit
- Pulse extension/freq.filter - 2.4 s / large 0.6 s / small 1.2 s / medium 0 s / off
- Retrievable parameters - Type Software revision Serial number Hardware revision Manufacturer
- Short circuit detection - only possible in the ON state.
- Short circuit input - < 50 µA
- Short circuit output - < 100 Ω
- Signal status bit - "0" = Output high-impedance "1" = Output is supplied
- Wire breakage input - < 50 µA
- Wire breakage output - < 100 Ω
Electrical Data
- Number of channels - 16 Ex i inputs/outputs Adjustable parameters in pairs
Explosion Protection
- Ambient temperature °C - -40 - 75 °C
- Application range (zones) - 1, 2, 21, 22
- ATEX dust certificate - DEKRA 12 ATEX0099 X
- ATEX gas certificate - DEKRA 12 ATEX0099 X
- Certificates - ATEX (DEK), Brazil (ULB), Canada (FM), EAC (STV), IECEx (DEK), India (PESO), Korea (KTL), USA (FM)
- Dust explosion protection ATEX - II (1) D [Ex ia Da] IIIC
- Dust explosion protection IECEx - [Ex ia Da] IIIC
- Ex interface zone - 0, 1, 2, 20, 21, 22
- Gas explosion protection ATEX - II 2 (1) G Ex ia [ia Ga] IIC T4 Gb
- Gas explosion protection IECEx - Ex ia [ia Ga] IIC T4 Gb
- IECEX dust certificate - IECEx DEK 12.0044X
- IECEX gas certificate - IECEx DEK 12.0044X
- Installation - Zone 1
- Ship approval - ABS, CCS, ClassNK, DNVGL, RINA
Galvanic isolation
- Aux. power/system components - ≥ 1500 V AC
- I/O channels / ground (PA) - ≥ 500 V AC
- I/O channels/system components - ≥ 500 V AC
- I/O module / I/O module - ≥ 500 V AC
- Test volt. for gal. separation - acc. to standard EN 60079-11
General
- Functional Description - The 9470/32 series digital input/output module for Zone 1 has 16 channels, which can be used in pairs for Ex i operation as inputs for contacts and NAMUR proximity sensors (EN 60947-5-6) or as outputs for indicator lamps and low-power solenoid valves. Eight inputs can be used for frequencies of up to 20 kHz, and four can be used for detecting the direction of rotation. All inputs/outputs are short-circuit proof and galvanically separated from the system.
- Highlights - Sixteen channels can be used in pairs as inputs or outputs intrinsically safe Ex ia IIC inputs/outputs with line fault monitoring and LED error and status indication for each channel module in Zone 1 can be hot swapped
- Product Description - Remote I/O IS1+ Digital input-output module For Zone 1 Ex i
- Product Type - 9470/32-16-11
- Title Product Variant Technical Data - 9470/32-16-11 DIOM 16 Z1 LED
- WebCode - 9470C
Input
- Counting range - 0 ... 65535 as UINT16
- Function - Up/down counter frequency with direction
- internal resistance - 1
- Max. input signal OFF - 1.2 mA
- Max. number counter inputs - 8
- Max. number frequency inputs - 8
- Min. input signal ON - 2.1 mA
- Min. pulse width - 25 Microsecond
- Number of inputs - 16
- operating point - 1.65 mA
- Resolution - 16 Bit / 32 Bit
- Signal input - input EN 60947 (NAMUR)
- Signal type - output input
- Supply voltage - 8.2 V
Mechanical Data
- Degree of protection IP (IEC 60529) - IP 20
- Depth - 67.000 mm
- Fire resistance (UL 94) - V2
- Length - 128.000 mm
- Module enclosure - Polyamide 6GF
- Pollutant class - Corresponds to G3
- Weight - 0.275 kg
- Width - 96.500 mm
Mounting / Installation
- Mounting position - horizontal vertical
- Mounting type - on DIN rail NS 35/15
- Mounting type 2 - (DIN EN 60715)
Output
- Application - low-power solenoid valves
- Internal resistance outputs - 1.0
- Max. number of outputs - 16
- Open-circuit voltage U a - 8.20 V
- Output current max. - 8.20 mA
- Output rated operation - 6 V / 2 mA
Safety Data
- Internal capacitance (1 Chan.) - 2.5
- Internal inductance L i - negligible
- Max. current I o (Ex ia) - 10.40 mA
- Max. power P o (Ex ia) - 25.50 mW
- Max. Voltage U o - 9.80 V
1 - 1 of 1 Part Numbers